Animal fat in slaughterhouses often penetrates concrete surfaces. If the fat is not removed before the concrete is coated, the fat can cause the coating to fail. How do you identify and remove the contamination before coating the concrete?


Selected Answers

From Glenn Summers of Conselcor Inc. on September 17, 2010:
Any contaminant within the gel-pore/capillary system of concrete has the potential to cause a coating failure. I take the approach that all concrete should be sealed from within the matrix prior to any coating operation. Identifying a contaminant type is not as important as is introducing a penetrating sealer to form a solid inside to stabilize the concrete. In the case of animal fats I have noted that, after a steam wash, my sealer will penetrate and expel fat from deep in the matrix up and out to the surface. Another wash to remove expelled contaminants is then followed by another application of the sealer to penetrate and form a solid in the capillary voids. Now I have a stabilized concrete that does not allow an internal chemistry or contaminant to compromise the surface bond of a coating.

From Luis Tapia of CPPQ on September 16, 2010:
Animal or another oil contamination is always a big problem to coating application over concrete surface. Concrete is porous and absorbs oil. You will know if there is oil on concrete by the water drop test, but I prefer dry methods like UV light. In my experience, a sucessfull way to resolve that problen is scarifying and resurfacing with an epoxy or cementicius grout. Other materials require use of water; and water on concrete will generate other problems because it stays for long time. Eng. Luis Tapia SSPC PSC Jet Flooring Systems CPPQ Peru.

From Jorge Lizarraga of International Paint on September 13, 2010:
Animal fat can be recognized using an ultraviolet light. If there is animal fat, we´ll see a blue fluorescence in the surface. We can remove it using a tensioactive in solution with water, and if the tensioctive isn´t enough, treat the surface with alternating washes with solvent(SSPC-SP 1) and tensioactives. I could wash several floors of a gas station, and then paint them succesfully.

Please sign in to submit your answer this question    

Tagged categories: Concrete


Current PSF Question | Submit a PSF Question | Full PSF Archive

Advertisements
 
Novatek Corporation
 
Dustless Coatings Removal
 
Novatek Corporation, Dustless Coatings Removal Strip, clean and profile all dust free! Comply with new lead standards. Contact today: (866) 563-7800 www.Novatekco.com
 

 
 

 
SAFE Systems, Inc.
 
Custom blast rooms
by SAFE Systems
 
Don't waste time and money "making do" with a "standard" design. Let us work with you to design and build the system that best fits your requirements.
Call 1-800-634-7278
 

 
BASF
 
New resins from BASF will have metals loving water!
 
Excellent corrosion resistance, low VOC, high gloss, thin films www.basf.us/industrialcoatings dpsolutions@basf.com 800-231-7868
 

 
KTA-Tator, Inc. - Corporate Office
 
New KTA Pipeline Inspection Kit
 
• Defelsko standard memory body
• Positector FTS 0-250 mils, cabled dry film thickness probe
• NEW Positector Shore D hardness probe
• All essential inspection equipment!
Visit www.ktagage.com
 

 
Bullard
 
Bullard Made in the USA
 
 

 
ABKaelin, LLC
 
ABKAELIN EH&S SERVICES
 
Programs/Training/Monitoring for Silica, Lead, Noise, Beryllium, Hexavalent Chromium, Cadmium, Hazardous Waste*PM10 & TSP-Lead Ambient Air Monitoring*SSPC C3/C5
 

 
North Dakota State University
 
Coatings Science Short Course – Registration Open
 
North Dakota State University, June 10 – 15, 2018. The course is designed for all levels of scientists and technologists working in the field of coating.
 

 
Absolute Equipment/Grand Rental Station
 
TIER 4 EQUIPMENT
 
We have Tier 4 Equipment including Air Compressors & Generators for Sale & Rent! Your job may now require Tier-4. www.absoluteequip.com or Call 412-931-6655.
 

 
 
 

Technology Publishing Co., 1501 Reedsdale Street, Suite 2008, Pittsburgh, PA 15233

TEL 1-412-431-8300  • FAX  1-412-431-5428  •  EMAIL webmaster@paintsquare.com


The Technology Publishing Network

Durability + Design PaintSquare the Journal of Protective Coatings & Linings Paint BidTracker

 
EXPLORE:      JPCL   |   PaintSquare News   |   Interact   |   Buying Guides   |   Webinars   |   Resources   |   Classifieds
REGISTER AND SUBSCRIBE:      Free PaintSquare Registration   |   Subscribe to JPCL   |   Subscribe to PaintSquare News
MORE:      About PaintSquare.com   |   Privacy Policy   |   Terms & Conditions   |   Support   |   Site Map   |   Search   |   Contact Us