Is the MEK rub test a conclusive test to check the cure of IOZ coatings?

More items for Quality Control


Selected Answers

From Simon Hope of Bilfinger Salamis on January 16, 2013:
     MEK rub test is only subjective as proof of cure for IOZ coatings. The test is only valid for the actual area tested and can only be applied to the whole item by extrapolation of result. Confidence in the result can vary wildly, depending on time, humidity and temperature, as the curing mechanism of IOZ is totally dependent on the integration of water into the silicate precursor to create the matrix to support the metallic zinc. Hence, the best advice is that once touch dry, fresh water washing enhances the cure mechanism. High humidity and water washing will give confidence and MEK rub then gives verification.

From wenbo chen of International Paint on January 15, 2013:
     Though ASTM D 4752 describes a standard test method for measuring MEK resistance of IOZ by solvent rub, we always use a coin test in the field. The MEK test is more likely a lab test.

From Chuck Pease of MMI Tank on January 14, 2013:
     Not conclusive, as Dave mentioned. Only a estimation. This requirement is per ASTM D 4752.  Note that in the 4th paragraph, line 2, they call it an estimation.

From Dipesh Vyas of CARBOLINE on February 15, 2013:
     My field expereince reveals that the coin test is the best, easiest,quickest most and reliable test to verify curing of spray- applied IOZ film. The MEK rub test, if not performed by a skilled person, can have misleading  results because spray-applied IOZ always has some loose zinc dust ( overspray), and if not cleaned will react with MEK  In first 5 passes, only satin will be noticed .

From Tom Schwerdt of Texas Department of Transportation on January 22, 2013:
     Wenbo, the MEK rub is certainly a field test - all you need is a rag, MEK and a finger! (Okay, a glove would be nice to have, too.) The MEK rub is more conclusive than the coin test. The only truly conclusive test is in the lab - generally a force cure in a sealed vial, followed by gas chromatography.

From Dave Lisnock of Arizona State University W.P. Carey Facilities on January 14, 2013:
     No, it is not  a conclusive test. The only true test is a lab test.

From Tom Schwerdt of Texas Department of Transportation on February 19, 2013:
     Dipesh - how crisp is the edge of your coin? How much force are you using? At what angle are you holding the coin? The coin test is at least as variable (if not more so) than the MEK rub test.

Please sign in to submit your answer this question    

Tagged categories: Curing; Performance testing


Current PSF Question | Submit a PSF Question | Full PSF Archive

HoldTight Solutions Inc.
NO FLASH RUST - NO CONTAMINANTS

Our HoldTight®102 salt remover & flash rust
preventer prevents flash
rust by removing surface contaminants. Contact us
for your nearest distributor.
(800) 319.8802 sales@holdtight.com


Fischer Technology Inc.
DUALSCOPE®FMP100 with DataCenter IP

Transfer customized inspection plans from PC to FMP100 using step-by-step guidance with prompts and pictures throughout the measurement procedure


Industrial Vacuum Equipment Corp.
Hurricane Vacuums
& Dust Collectors

Vacuum and dust collector hose, filters and related accessories.
IndustrialVacuum.com


SAFE Systems, Inc.
Custom blast rooms
by SAFE Systems

Don't waste time and money "making do" with a "standard" design. Let us work with you to design and build the system that best fits your requirements.
Call 1-800-634-7278


DeFelsko Corporation
PosiTector SST Soluble Salt Tester

Measures the concentration of soluble salts on metal surfaces. Use with all Bresle patch types including the reusable, adhesive-free PosiPatch.


KTA-Tator, Inc. - Corporate Office
KTA-TATOR LABORATORY SERVICES

• Coating failure analysis
• Independent
  comparative testing
• Accelerated
  weathering testing
• Toxic metals testing
• A2LA Accredited
Contact: Cindy O'Malley,
at 412-788-1300 x180


SSPC: The Society for Protective Coatings
http://www.sspc.org/

Join SSPC and Enhance
Your Career !


Covestro Deutschland
Corrosion protection – one layer ahead

Pasquick® saves one layer of coating in corrosion protection projects – resulting in faster workflows and more cost efficiency for owners and contractors.


PreTox Products - NexTec, Inc.
GOT LEAD? Specify Pretox System products

The ONLY Lead Stabilizer Compatible with All Paint Removal Methods. Works with all Blast Media: Grits | Recyclable Abrasives | CO2 | Water | Power Tools | Etc. Call Dave Steffen at 800.338.8296.


Tarps manufacturing, Inc.
QUALITY MADE IN AMERICA —Available near you!

CLICK to get a behind-the-scenes look at how Tarps Manufacturing makes the highest-quality tarps right here in the USA — available nationwide.

 
 
 

Technology Publishing Co., 2100 Wharton Street, Suite 310, Pittsburgh PA 15203-1951

TEL 1-412-431-8300  • FAX  1-412-431-5428  •  EMAIL webmaster@paintsquare.com


The Technology Publishing Network

Durability + Design PaintSquare the Journal of Protective Coatings & Linings Paint BidTracker

 
EXPLORE:      JPCL   |   PaintSquare News   |   Interact   |   Buying Guides   |   Webinars   |   Resources   |   Classifieds
REGISTER AND SUBSCRIBE:      Free PaintSquare Registration   |   Subscribe to JPCL   |   Subscribe to PaintSquare News
MORE:      About PaintSquare.com   |   Privacy policy   |   Terms & conditions   |   Site Map   |   Search   |   Contact Us